PCU Uninterruptible Power Supply General Features | ||
---|---|---|
Power (kVA) | In the range of 2KVA - 200KVA, at certain powers | |
Technology | Actual Double Conversion Technology with IGBT | |
Power Factor | 0.70 | |
Input | ||
Rated Input Voltage | 220VAC 1Phase+Neutral+Ground | 380VAC 3Phase+Neutral+Ground |
(Different voltage values are optional) | ||
Voltage Tolerance | -%15 , +%15 | |
Frequency | 50 Hz. +/-%5 (60 Hz. optional) | |
Output | ||
Voltage Range | 220VAC 1Phase+Neutral+Ground | 380VAC 3Phase+Neutral+Ground |
(Different voltage values are optional) | ||
Voltage Tolerance | +/-%1 | |
Overload Capacity | For 125% 60sec., for150% 5 sec., for 200% 0.1 sec. | |
Efficiency | > 85% | |
THD | <3% | |
Transformer | Output Galvanic Isolation Transformer | |
By-Pass | Uninterruptible Static By-Pass and Maintenance By-Pass switch | |
Management and Communication Interfaces | ||
Operator Panel | LCD Display Panel, Input Voltage, Output Voltage, Load Percentage,Frequency, Battery Voltage, Fault and Status information, Light and Audible Warnings | |
Remote Management Interface | Browser-based remote monitoring with Ethernet connection (optional) | |
Protection Functions | ||
Overload Protection | Electronic Overload Protection | |
Current Protection | Input Circuit Breaker and Output Circuit Breaker | |
Over Temperature Protection | Electronic Over Temperature Protection | |
Environmental Conditions | ||
Operating Temperature | -10 °C ~ +40 °C | |
Altitude Operating Height | 1.500m | |
Humidity | 90% none condensed | |
Cabinet Specifications | ||
Type-Protection Class | Specially designed cabinet, IP21 Indoor type | |
Paint-Color | Epoxy-Polyester Powder Paint RAL-7032 | |
Cooling | Forced air cooling with thermostat controlled fan |
OPTION | CODE | DESCRIPTION |
Non-standard input voltage value | xxxV | PCU Uninterruptible Power Supply and Inverter can be produced at any required input voltage value that must be stated clearly by the order confirmation. |
Non-standard output voltage value | xxxV | PCU Uninterruptible Power Supply and Inverter can be produced at any required output voltage value that must be stated clearly by the order confirmation. |
Adjustable output voltage | ADJ | Output voltage of PCU Uninterruptible Power Supply and Inverter can be adjusted by the LCD panel. Maximum adjusting range is +/-15% |
Inverter application | IA | PCU Uninterruptible Power Supply Inverters can be produced as DC/AC inverters for special applications. Input-Output Voltage and Frequency parameters can be adjusted accoring to project needs. |
High capacity Battery Charging | HCB | The battery capacity of the PCU Uninterruptible Power Supply and Inverter can be increased according to the project needs |
Non-standard frequency | FRQ | PCU Uninterruptible Power Supply and Inverters are produced to function with 50Hz network frequency. If 60 Hz is required this must be stated cleary order confirmation. |
Output protection CB | OCB | Optional MCCB may be added to the Uninterruptible Power Supply and Inverter output to provide additonal protection. |
IsolotionTransformer | TRF | Isolation Transformer or Voltage Changing Auto-Transformer can be supplied for both input and output of PCU Uninterruptible Power Supply and Inverters. Reguired transformer specifications must be given by the order |
Redundant Operation | RO | The PCU Uninterruptible Power Supply and Inverter can be used to operate redudantly with up to 2 units. |
Special Enclosure | K | The PCU Uninterruptible Power Supply and Inverter can be produced both INDOOR and OUTDOOR in special cabinets having different IPXX protection classes. |
EMC Filter | EMC | Specially designed EMC-Filters can be added optionally to the both input and output of The PCU Uninterruptible Power Supply and Inverter . Filter specifications must be stated by offer/order. |
Surge Arrester | ESD | High-Voltage Protection and Surge Arrester can be added to the both input and output of The PCU Uninterruptible Power Supply and Inverter . The required protection classes and the specifications (CLASS-I,CLASS-II,CLASS-III) must be given with the order. |
Remote monitoring and management unit | RMU | For remote monitoring and managing of The PCU Uninterruptible Power Supply and Invertor , Remote Management and Monitoring unit can be added optionally. No any other software is needed for this RMU unit which provides a browser based communication over LAN- connection or internet. |
Dry contacts | C | Dry Contact outputs can be added to the PCU Uninterruptible Power Supply and Inverter for remote monitoring |
Special design and accessories | SPM | PCU Uninterruptible Power Supply and Inverter can be designed specially with respect to direct customer needs and technical specifications. All special requirements and detailed technical drawings and specifications for accessories must be provided by the customer at the offer/order stage |
Special operating temperature | SOT | Custom devices those can operate in special operating temperatures can be manufactured on demand. |